Abstract
The paper presents a fast and accurate technique for ranking transmission line outages according to the severity of their effects on busbar voltages. To simulate each contingency case, the proposed technique uses the DC formulation with compensation method to compute the post outage angle and the superdecoupled load flow formulation, and compensation method to derive the post outage voltage. The quadratic voltage performance index for every line contingency is then computed, and the results are subsequently sorted in descending order, according to the severity of effects. Computational results of this technique, applied to different test systems, are presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEE Proceedings C Generation, Transmission and Distribution
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.