Abstract
Herein, we successfully designed a ventilation system for a new 350-MW air-cooled turbogenerator based on a reasonable lectotype choice and optimization analysis. Fluid field and thermal analysis based on computational fluid dynamics were performed to guide the optimization of cooling structures and ensure temperature rise under the limit of insulation grade B. The measured values obtained from recent factory assembly-type testing were found to coincide with the design expectations for generator efficiency and temperature rise. The results confirmed the feasibility of a multi-chamber forward-flow cooling path for 400-MVA-class air-cooled generators.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.