Abstract

A new physics-based and modular variable refrigerant flow (VRF) heat pump model aimed toward multi-year simulations is presented. The model allows the simulation of any number of indoor units (IU), outdoor units (OU) and compressors. A parameter-estimation procedure and a control strategy both using available manufacturer data is proposed. The model is validated against data collected from a VRF system that services the first floor of the former ASHRAE Headquarters Building in Atlanta (USA), comprised of 22 IU, 2 OU, and 8 compressors. Results show that the model accurately predicts the total energy consumption over a two-month cooling period, with a relative error, normalized mean bias error, and coefficient of variation of the root mean square error of 1%, 1.6%, and 16.7%, respectively.