Abstract

Neutral point clamped (NPC), three level converters with insulated gate bipolar transistor devices are very popular in medium voltage, high power applications. DC bus short circuit protection is usually done, using the sensed voltage across collector and emitter (i.e., VCE sensing), of all the devices in a leg. This feature is accommodated with the conventional gate drive circuits used in the two level converters. The similar gate drive circuit, when adopted for NPC three level converter protection, leads to false VCE fault signals for inner devices of the leg. The paper explains the detailed circuit behavior and reasons, which result in the occurrence of such false VCE fault signals. This paper also illustrates that such a phenomenon shows dependence on the power factor of the supplied three-phase load. Finally, experimental results are presented to support the analysis. It is shown that the problem can be avoided by blocking out the VCE sense fault signals of the inner devices of the leg.