Abstract

From long-term real-time radon and radon progeny measurements taken in a relatively large retail store, cyclical patterns were evident, which were found to relate to the overriding influence of the timed air-conditioning system. Concentration of radon, radon progeny and the variability of F factor were found to depend significantly on the intermittent operation of this ventilation/air-conditioning system. After pressure equalisation remedial measures proved ineffective, the air-movement system was utilised to reduce the levels of radon and radon progeny to well within established norms applicable during working hours. It is demonstrated that the average levels for radon and radon progeny are reduced in absolute terms. This amounted to less than 12% of the general level, during designated work periods. Where air movement systems are already installed, as well as other circumstances, their regulation provides an economical solution to meeting legal and other standards for radon in the workplace.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.