This paper presents a novel discrete-time sliding-mode control algorithm for an uninterruptible power supply (UPS) inverter design. The approach offers a dual-loop design, in which a current predictor utilizes the tracking error of output voltage to estimate the desired inductor current, while a current controller is adopted to regulate the inductor current and, thus, produces a control command to the pulsewidth modulation inverter. An explicit condition for stable controller design is derived. The efficacy of this scheme is validated via a successful implementation on a digital-signal-processor-based UPS inverter. The proposed scheme has shown its robustness on low output voltage distortion, excellent voltage regulation, and it is insensitive to load variation, even under nonlinear loads. Experimental studies were performed to further validate the effectiveness of this scheme.