Abstract

Smart-grid applications based on synchrophasor measurements have recently been shown to be vulnerable to timing attacks. A fundamental question is whether timing attacks could remain undetected by bad-data detection algorithms used in conjunction with state-of-the-art situational-awareness state estimators. In this paper, we analyze the detectability of timing attacks on linear state-estimation. We show that it is possible to forge delay attacks that are undetectable. We give a closed form for an undetectable attack; it imposes two phase offsets to two or more synchrophasor-based measurement units that can be translated to synchrophasors’ time delays. We also propose different methods for combining two-delays attacks to produce a larger impact. We simulate the attacks on a benchmark power-transmission grid, we show that they are successful and can lead to physical grid damage. To prove undetectability, we use classic bad-data detection techniques such as the largest normalized residual and the ${\chi ^{2}}$ -test.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.