Abstract

When single-line-to-ground fault happen in neutral non-effectively earthed system, there is a big difference between the fault feeder and un-fault feeder in transient signal energy centralized frequency band and signal amplitude of fault phase. The transient signal energy in fault feeder’s fault phase is bigger, and it centralizes in lower frequency band. But the transient signal in un-fault feeders’ has the contrary features. And this feature is affected little by the fault initial angle. So the paper proposed a method that using the gravity frequency and transient signal energy to form a two-dimension line selection method that using the signal overall distribution characteristics. It can be applied in neutral unearthed and resonant system simultaneously. And the method is effectively to different fault initial angle and fault resistance. The method is proved correctly, effectively and adaptively by actual simulation in different fault cases.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.