Abstract

ABSTRACT This paper examines precision of predicting time responses for torque in turbine-generator-exciter shafts together with fatigue life expenditure of shafts by frequency domain analysis not analysed in the literature heretofore following incidence and clearance of worst-case disturbances on the electrical supply system. Effect of both governor and avr action following a range of disturbances is also illustrated. The effect of steam and electrical viscous damping on maximum and minimum shaft torques predicted by frequency domain analysis for a range of disturbances as a function of the fault clearing time is also depicted The analysis is based on Fourier analysis of generator airgap torque following incidence and clearance of a severe supply network disturbance or following mal-synchronisation to obtain torque excitation which acts on the generator rotor corresponding to each modal vibration. Amplitude and phase of each modal vibration is thereby determined. Using appropriate damping, time responses...

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.