Abstract

Double-circuit current comparison protection (DCCCP) is an algorithm for travelling-wave-based protection of a double-circuit high-voltage line. It uses the balance between the two circuits to distingush between an internal fault and an external disturbance. To prevent incorrect trips superimposed currents are used, and the relay has to be blocked after detecting an external disturbance. The setting of relay parameters is discussed, as well as its performance. The tripping time is between 100 and 200 μs for the majority of faults. For faults around voltage zero, the tripping time is between 1 and 3 ms, depending on the amplitude of the short-circuit current. Faults close to the remote line terminal are not detected at all. Some direct lightning strokes will lead to an incorrect trip. To overcome the disadvantages of DCCCP, it is combined with travelling-wave-based differential protection in a protective scheme. Differential protection is a somewhat slower but very reliable backup. Its parameter setting is discussed, as well as its performance. The tripping time is between 1 and 3 ms. The protective scheme further contains fast reclosure, breaker-failure detection and adaptive setting for the backup relays.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.