Transient stability analysis is a traditional yet significant topic in power systems. The switching control schemes of the HVDC converter station after fault bring new challenges to the direct method of transient stability analysis in AC/DC power systems. To apply the direct method to investigate the transient stability of power systems accommodating the switching characteristics of the line commutated converter (LCC) HVDC, continuous piecewise Lyapunov functions are constructed for a whole AC/DC system model including several classical LCC-HVDC control modes, and the continuity of Lyapunov functions is studied and guaranteed in transitions between control modes. Then, the Sum-of-Squares optimization is employed to find the optimal continuous piecewise Lyapunov functions. Finally, the transient stability domain is estimated for a sample system including the main control loops of LCC-HVDC, a three-order generator model, and a one-order exciter model. Tests in MATLAB environment are conducted to demonstrate the feasibility of this method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.