Abstract
Fast dynamics and transient events are becoming more and more frequent in power systems, due to the high penetration of renewable energy sources and the consequent lack of inertia. In this scenario, Phasor Measurement Units (PMUs) are expected to track the monitored quantities. Such functionality is related not only to the PMU accuracy (as per the IEC/IEEE 60255-118-1 standard) but also to the PMU reporting rate (RR). High RRs allow tracking fast dynamics, but produce many redundant measurement data in normal conditions. In view of an effective tradeoff, the present paper proposes an adaptive RR mechanism based on a real-time selection of the measurements, with the target of preserving the information content while reducing the data rate. The proposed method has been tested considering real-world datasets and applied to four different PMU algorithms. The results prove the method effectiveness in reducing the average data throughput as well as its scalability at PMU concentrator or storage level.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.