Abstract

A push-pull ventilation system is effective for hazardous material exhaustion. Although a push-pull ventilation system has advantages over a local exhaust hood, some laborious adjustments are required. The pertinence of the adjustments is uncertain because it is difficult to evaluate the performance of a push-pull ventilation system quantitatively. In this study, a measurement of the capture efficiency of a push-pull ventilation system was carried out by means of a tracer gas method. The capture efficiency decreased to 39.3-78.5% when blockage material, a dummy worker and a cross draft, were set in the ventilation zone, but the efficiency was 95.1-97.9% when the cross draft was stopped. The results suggest that the uniform flow of a push-pull ventilation system will detour a blockage and the performance of the system will not be reduced unless a cross draft disturbs the uniform flow.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.