Parallel redundancy protocol (PRP) and high-availability redundancy protocol (HSR) are widely adopted protocols based on IEC 61850 standard to support zero recovery communication networks for time-critical and reliable interactions in power system substations. However, hiring these protocols comes with technical and economic constraints that impact the size of the substation network arrangement. Therefore, we will undertake a theoretical analysis of HSR, PRP, and their combinations to reach a maximum number of nodes in different substation communication architectures regarding IEC 61850 standard message time constraint requirements and IEC 62439-3 standard regulations. We will validate our findings through a simulation in the OPNET Modeler environment. In addition, we considered bandwidth efficiency by prohibiting the extra circulation of packets in the redundancy Box (RedBox) and QuadBox implementation as interfaces for HSR and PRP connection and HSR rings interconnection, respectively, which represent the main hindrance in utilizing the combination of these protocols.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.