Abstract

This study attempts to verify the accuracy of energy savings prediction using a daylight responsive dimming system. To accomplish this, the real-time power consumption of electrical lighting in a mock-up space was compared with the power consumption that was calculated using ‘the prediction method’ (Method A), which was suggested to improve the accuracy of the predicted amount of energy savings. In addition, this study suggested the ‘indirect illuminance’ concept (Method B) to improve the system performance and predict the lighting energy savings potential of a system because certain inherent problems that are caused by the open-loop proportional control algorithm used were identified. Regarding the accuracy of the prediction method, ‘Method A’ considers the non-linear dimming curve of the luminaires and thus generated data that were more similar to the real measured lighting power consumptions. ‘Method B’ generated higher energy savings potential (e.g., 36.9–73.8%) compared with those of Method A (e.g., 27.6–72.9%) on each day.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.