Abstract

Derivative method, which avoids pathological solution of the magnetic field inverse problem, was proposed to solve the problem of drawing loss or unknown of grounding grids. First, a shape function was introduced to describe the distribution of magnetic field which is perpendicular to the surface of grounding grids. Since its odd-order derivatives contain main peaks, the 1st-, 3rd- and 5th-order derivatives were chosen to solve the topology of substation grounding grids and measure the branch current of the grid by determining the position and value of main peak, respectively. Numerical example and experimental result show that the 1st- and 3rd-order derivative method works well with low error and less computation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.