Abstract
The overall noise level measured from chiller units is controlled by primarily tonal noises from (1) the fans, (2) the compressors, and (3) the associated pipework. Three large chiller units were measured using AHRI 370 methodology to quantify the overall sound level spectra and A-weighted sound level from different chiller units in a range of environmental conditions. Whilst this method can identify a general area of tonal emission to within a couple of meters across a unit’s surface that is emitting discrete tonal noises, the method is limited when there are multiple potential tonal sources. Sound intensity imagery was used on two units to quantify the overall sound power emanating from the source, but also to offer a more advanced method of localizing the source of discrete tones to aid in the application of mitigation treatments. Results presented include visually displaying and quantifying the location of noise emission from fan blade pass frequencies and associated harmonics, localization of problematic tones emanating from individual pipework junctions and valves, and the reductions in sound power emissions achieved from lagging compressors and pipework.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.