Abstract

The transmission tower is an important infrastructure for transmission lines. To secure the operation of the power grid, it is particularly important to evaluate the safety of the in-service transmission tower under the action of random wind loads throughout their entire life cycle. Thus, this paper firstly establishes the time-varying equivalent performance function of the in-service transmission tower under the action of random wind loads. Then, in order to address the shortcomings of the traditional maximum entropy method, the high-order moments-based improved maximum entropy method (HM-IMEM) is proposed and extended to assess the wind resistance global reliability of the in-service transmission tower. Finally, the effectiveness of the proposed method is demonstrated evaluating the wind resistance global reliability of an in-service transmission tower in an engineering setting. Analytic results indicate that: (1) The proposed method can ensure a balance between calculation accuracy and efficiency. Compared with Monte Carlo simulation (MCS) method, the relative error is only 0.11% and the computational cost is much lower than that of the MCS method. (2) The reliability of the in-service transmission tower significantly decreased over time. In order to guide maintenance and reinforcement by predicting the time-varying performance of in-service transmission towers, it is of great engineering value to evaluate the wind resistance global reliability of the in-service transmission tower.