Abstract
Using the framework of the first and second law of thermodynamics, an ejector–vapour compressor cascade refrigeration system is studied. The criteria for refrigerant selection are examined, with R134a and R410A selected as the refrigerant for the ejector and compressor sub-cycle, respectively. The effects of generator temperature, evaporator temperature, condenser temperature, intercooler temperature and intercooler temperature difference are examined. The results demonstrate that a combined cycle can improve 30.8% when compared to the COP of single compressor cycle and 122% when compared to the single ejector cycle. In addition, intercooler temperature can be set at 26.5 °C for minimizing total exergy loss.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.