Abstract
Abstract The aim of this work is to evaluate the performance of an intermittent personalized ventilation (IPV) system assisting a displacement ventilation (DV) system to improve thermal comfort and save energy. This will be conducted by developing a transient 3D computational fluid dynamics (CFD) model of an occupied office space equipped with systems. The occupant is modeled by a heated thermal manikin replicating the human body. The CFD model is coupled with a transient bio-heat model to compute segmental skin temperatures and their rate of change. The latter are taken as input into Zhang’s comfort model to predict and overall thermal comfort. The model was used to conduct a case study, where the overall thermal comfort and energy savings will be assessed for the IPV + DV These results will be compared with those of steady personalized ventilation (PV) + DV and standalone DV systems. By varying the IPV frequency in the typical indoor range of [0.3 Hz – 1 Hz], it was found that the IPV + DV system was able to enhance comfort compared to steady PV + DV and a standalone DV. In addition, an energy analysis was conducted and it was shown that the IPV was able to achieve considerable energy savings compared to a steady PV + DV at the same thermal comfort level. Moreover, relaxing the DV supply temperature to higher occupied zone temperatures, can provide additional energy savings while still maintaining comfort levels in the space.