Abstract
Delayed activation of the sprinkler or water film system may accelerate the crack and fallout process of the heated glass when encountered in a fire. A series of tests were conducted to investigate the thermal breakage and fallout behavior of a non-tempered glass façade with down-flowing water films. The most widely used non-tempered glass, low emissivity coated glass (Low-E), and float glass were studied in this work. An n-heptane pool fire was employed to heat up the glass panes and the water film was acted when the maximum glazing temperature reached the different designed values. The results illustrate that water film has little influence on the fracture behavior of float glass. However, the water film does accelerate the crack and fallout process of Low-E glass significantly when the glazing temperature is over 70°C. This is because large thermal stress is generated inside the glass due to the continuous cooling of the cold water film, which exceeds the ultimate tensile stress of glass. The water film also has a large impact on the crack propagation and fallout ratio of the glass panes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.