Abstract

This paper proposed a double ejector-expansion autocascade refrigeration cycle (DEARC) using hydrocarbon mixture R290/R170 for applications in low-temperature freezers. In DEARC, the two ejectors are introduced to reduce the thermodynamic loss in throttling process. The performances of the traditional autocascade refrigeration cycle (ARC), single ejector-expansion autocascade refrigeration cycle (EARC) and DEARC are compared, and several important parameters for DEARC are also discussed in detail. The results indicate that DEARC is feasible and there are obvious performances improvements on theCOP, volumetric refrigeration capacity and exergic efficiency. Especially, in DEARC, the COP increases by 97.9% and 29.6% at most compared to that of ARC and EARC, respectively, the volumetric refrigeration capacity is 334.8% and 188.6% higher than that of the two cycles. In general, the DEARC provides obvious performance improvement and produces better actual operation benefit. The potential practical advantages may be worth further attention in future studies.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.