Abstract

This paper discusses the role of high voltage direct current (HVDC) voltage waveforms on partial discharge (PD) activity in paper/oil insulation systems. A variety of voltages were simulated by the PSIM software and synthesized using a high voltage amplifier. Kraft paper sheets were used to create defects incepting PD. The PD signals were coupled by a high frequency ferrite core current transformer. PD quantities including PD inception voltage (PDIV), pattern, amplitude distribution and repetition rate were recorded. The results show that the PDIV under notched voltage becomes higher increasing firing and overlap angles. PD patterns change with the HVDC voltage waveforms showing that large PD likely occurs at the rising front of the notches. PD amplitude and repetition rate are both directly proportional to notch depth. It is expected that such results can improve the design of UHV converter transformers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.