Abstract

When single phase-to-ground fault happened in power network with arc suppression coil grounded, capacitor current through fault point is compensated and reduced by installing arc suppression coil. Zero-sequence current’s amplitude and phase of fault lines and sound lines are so similar that it increases the difficulty of selecting the fault line. But the resistance component of zero sequence current has no relationship with the arc extinguishing coil compensation, absolute value of resistance component to the fault lines show the maximum, and zero sequence current’s polarity of fault lines is contrary to sound lines. In this paper, because of the characteristic of resistance component, a method is put forward based on zero sequence energy to the line selection in distribution network, it import auto-reclosing techniques into the line selection. The principle is verified by MATLAB simulator. It has high accuracy to select the fault line with this method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.