Abstract
The healthy state of insulation in oil-impregnated bushings is traditionally evaluated by tanδ and capacitance at power frequency and mostly at 10 kV in the test standard. However, there has frequently been insulation accidents induced by moisture ingress (MI) for bushings that have passed the standard. The mechanism and new diagnostic features for MI into bushings were not distinct enough and an accurate test method is urgently needed research. To address this technical gap, a bushing model with a transparent sheath was designed and an ultrasonic humidifier device was adopted to simulate the environment of MI in bushings and recorded by digital camera. The parameters of dielectric dissipation factor, capacitance, partial discharge (PD), frequency domain response, and moisture content in oil were measured at room temperature with time. The results presented that both the increment dissipation factor at low frequency of 0.001 Hz and the increment dissipation factor of 1.2 Um could be used for detecting the earlier insulation defect of oil-impregnated paper (OIP) bushings. The phase resolved partial discharge (PRPD) can serve as the diagnostic basis of the severe state (S3) of insulation deterioration caused by MI into bushings around the phases of 0–117°, 151–303°, and 325–360°. The research findings would provide a useful reference for the condition diagnosis and maintenance of OIP bushings. Especially, the increment detection of Frequency Domain Spectroscopy (FDS) at the frequency of 1 mHz and 10 kHz was recommended firstly for the operative bushings in real sites.
Highlights
The oil-impregnated paper (OIP) condenser bushing is the most common device for power transmission in service
As has been frequently reported, the failures of OIP bushings could be induced by moisture ingress (MI), which might initiate a partial discharge (PD) and even explosion accidents of the power apparatus in a substation [3,4]
After MI into the bushing, the tanδ of the bushing model was increased from 0.62% to 0.73% under the AC voltage of 10 kV
Summary
The oil-impregnated paper (OIP) condenser bushing is the most common device for power transmission in service. It was found that capacitance measurements at power frequency were not sensitive distinct enough in order to detect insulation accidents induced by MI for bushings, which passed the enough to detectstandards. It was found that capacitance measurements at power frequency were not Victor Sokolov [15,16] from ZTZ-Service studied the typical defect and failure modes of HV bushings sensitive enough to detect the changes in moisture content. M. Krüge [14] from OMICRON Energy and modified the equivalent of the dissipation factor to diagnose the local moisture contamination measured the new and aged bushings using the Frequency Domain Spectroscopy (FDS) method, of bushings. The moisture content in the paper of the bushing model was measured until PD obviously maintenance of OIP bushing in the power system. It was expected that the test results could provide applicable reference for condition monitoring and maintenance of OIP bushing in the power system
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have