Abstract
We present the influence of the cooling tower airflow inlet region modifications at the Sostanj 4 thermal power plant on cooling tower local efficiency. Local efficiency change was estimated based on temperature fields of drift eliminators before and after the reconstruction of the cooling tower. Temperature fields were measured with thermal vision method. The local reduction of cooling tower efficiency was analyzed based on phenomenological relations of heat transfer obtained from the selected vertical segment of the cooling tower. The characteristic influence that the reconstruction had on the temperature field was detected on the circumference of the cooling tower. The efficiency reduction was the highest on the periphery of the cooling tower and in particular section it peaked at 2%, while in most part of the area it was below 0.5%. The presented measurement and analysis method enables the estimation of changes in the local efficiency of heat transfer in cooling towers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Strojniški vestnik – Journal of Mechanical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.