Abstract

This paper studies the effect of the soft feedback in hydro-turbine and its governor system on power system transient stability. Low frequency oscillation phenomenon in which the hydraulic turbine sets participate occurred on power system many times this year, which with no mechanism discovered. In this paper, we first study the effect of mechanical load moment output of the prime mover system on the mechanism of low frequency oscillations, then by analysis of small-signal stability on hydro-turbine and its governor system and simulation experiments on an two-generator power system using PSASP, we come to the conclusion that: If the soft feedback output values of hydro-turbine governor systems are set small in the power system, it will come to the unstable oscillation condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.