Abstract

The mechanism of power system low frequency oscillation was discussed in this paper. The coupling model between turbine governor system of plant and power system was established in MATLAB. The possibility of power system low frequency oscillation induced by unit-grid coupling was researched in detail. The simulation results indicate that power system low frequency oscillation will occur under disturbance, if a high derivative gain is used in PID controllers of hydraulic turbine governing system and partial derivative of turbine power output with respect to head varies with load. As for steam turbine, the PID parameters of governor system have important effect on small-signal stability of power system when the damp of power system is not very strong. The power oscillations caused by disturbance is decreased with the use of PID controller in governing system, whereas power oscillation is increased with the use of PI controller.