Abstract

A high penetrating the capacity of Rooftop PLTS has an impact on the performance of distribution network operations and the prior technical studies only using simulation. This paper examines the impact of integrating a 1.1 MWp PV Rooftop into the medium voltage distribution network, involves a comparison between simulation data obtained using the ETAP software, before and after integration, compared with direct measurements. The results indicate improvements in the distribution operating performance. Following the integration, there was a 0.05% increase in voltage levels, a 0.06% increase in short circuit current, a 1.25% reduction in network losses, up to 8.9% harmonics current, up to 0.14% harmonics voltage, and a 0.28% decrease in power factor, as observed at both the substation and the network, they are in accordance with the measurement results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.