Abstract

This paper presents an experimental study of fire suppression effectiveness with water mist containing FeCl2 additives.The investigation focuses on suppression effectiveness under various FeCl2 additives concentrations,working pressures and nozzle different height above the fire source . The experimental results show that: there is a significant impact on fire suppression effectiveness when adding FeCl2 to water mist. There is an optimum additive concentration of extinguishing fire, corresponding to the shortest extinguishing time, the least amount of water, the highest efficiency of extinguishing fire. The nozzle working pressures and nozzle position have effect on the performance of the water mist extinguishing: the greater the pressure is, the shorter water mist fire extinguishing time is. Under the same experimental conditions, the closer the water mist nozzles are to the oil pan, the shorter extinguishing time is.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.