Abstract

The effect of flow coefficients, working pressures, nozzle layout and aircraft angle on extinguishing aircraft cabin fire by water mist were studied by experiment. The results show that the fire suppression effectiveness is increased with the increase of flow coefficient and working pressure; the diamond-shaped layout in sprinkler is better than square layout,and the aircraft angle of 30° is better than of 10°or 20°.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.