Abstract

This paper presents a study on the voltage and electric fields behaviours of a 10kV polymer insulator with moss deposited under dry (air) condition. The aim of this study is considering on the electrical behaviour of insulator by having a surface layer of moss on it that can change the withstand voltage of insulators. It should be mentioned that these moss layers are commonly crated in the jungles especially in the tropical countries. To study on the above mentioned case, simulations were carried out using ANSYS High Frequency Structure Simulator (HFSS). The simulation insulator modelling includes the computerized evaluation of voltage and electric field distribution at three different locations for both clean and moss contaminated insulators. Noted that the electric field and also voltage profiles at different parts of insulators has been determined using applied simulated model. The moss contamination polymer insulator displayed a discontinuous distribution of the electric field compared to the clean insulator and their voltage distribution decreased with distances from the source. The results indicated that electric field along the insulator surface were greatly affected by hydrophobicity characteristic of the polymer. Therefore, the surrounding air of the moss contaminated insulator was prone to initiate a flashover. This study can be helpful for designing the distribution lines especially in high risk areas to set a proper design from the point of view of insulation coordination.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call