Abstract
To ensure its availability and service reliability, a ca- pacitor bank requires thorough protection that will result in min- imal damage to the bank and ultimately to the power system. A faulty bank should be removed from the system before it is exposed to severe damage or before a fault is established on the system. Normal capacitor bank protections should include individual unit overcurrent protection, overcurrent protection, rack faults protec- tion, and overvoltage protection. IEEE C37.99-1990 indicates that the present protection schemes, especially for double-Y banks, are not very effective for rack faults. The proposed protection scheme in this paper has a novel approach to the protection of the capac- itor banks. It modifies the impedance relay scheme to achieve the capacitor bank protection function with reliability. The discussions and results presented in this paper can be applied for both single- and double-Y capacitor banks.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.