This paper describes capacitor bank design, transient studies, protective relaying considerations, and operating experience. Associated with an application of high voltage capacitor banks. A 500 kV capacitor application and a 230 kV fuseless capacitor bank are presented as examples of developments in the design and protection of shunt capacitor banks. In addition, this paper presents the most significant findings of a large transient study completed to evaluate the impact of the 500 kV application. Operation experience is presented for a 500 kV zero voltage closing relay in combination with a preinsertion resistor used for transient suppression during closing. Analysis of a restrike failure of a 500 kV arrester is discussed along with field testing of a fuseless capacitor bank. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.