Abstract

It is shown that the optimum design of duct in a magnetohydrodynamic generator is close to the one in which the flow Mach number remains constant. This constant-Mach-number generator is analysed in some detail and it is shown that the optimum Mach number can be defined to within a few percent. For a γ of 1·25, this optimum is near 0·85. For very short ducts, the maximum power output is obtained near matched-load conditions but for rather longer ones maximum total power output is obtained by working as close to short-circuit conditions as is practicable. Against this, the minimum compressor requirements are found by working as close to open-circuit conditions as is practicable, and so a compromise must be reached for optimum overall generator design as far as load conditions are concerned. This will probably give an internal ohmic loss in the fluid of about one-third of the total output. Curves are presented which enable the optimum Mach number to be determined with greater precision when the optimum load conditions have been selected.