Abstract

The electrical performance of outdoor insulation degrades severely during combinations of factors that include surface contamination (C), ice (I), fog (F) and an ambient temperature that rises through 0 C (T{sub 0{degree}}). Failures at operating voltage on 115-kV, 230-kV and 500-kV systems occur with increasing probability under these conditions. A new CFT{sub 0{degree}} or cold-fog test method has been developed to reproduce the flashovers at all three voltage levels. Three options are identified for improving CFT{sub 0{degree}} performance: use of semi-conductive glazes, substitution of silicone for porcelain and use of silicone coatings on existing porcelain insulators.