Abstract

This paper analyzes used in wye-delta connected transformer differential protections, impacts of these current compensation methods to identify inrush current under different conditions of occurring inrush, i.e. single phase, two phases and three phases, are studied. Based on the simulation of MATLAB, this paper emphasizes the second harmonic component contained in differential current when transformer is energized without loads, and concludes that the compensation methods only using currents in wye side of transformer has the same effect to discriminate inrush currents compared with other two compensation methods. In addition, It analyses the relationship between the first and second harmonic components contained in the differential current, and points out that the method using phase angle in the second harmonic component in differential current is not suitable for three different current compensation methods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.