Abstract
To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers. However, the main problems of the current comparison method are in the very high inrush currents and relatively small fault currents regarding winding short circuits. Also The second harmonic component in fault current is increased in long lines which may blocks the relay operation. This paper describes a method to discriminate internal fault from inrush current and faults with a high second harmonic component by the sum of active power flowing into the transformer from each terminal. The average power is almost negligible for energizing, but an internal fault consumes large amounts of power.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.