Abstract

Temperature rise tests on standard single-phase, oil-filled distribution transformers are compared for sinusoidal and nonsinusoidal current conditions. In addition to a stock 50 kVA unit, two 25 kVA transformers were specifically constructed with embedded thermocouples that permitted the true hot-spot temperatures to be measured under load. Test results show that when subjected to full-load currents having low-order harmonic distortion values up to 40 percent THD, the average winding temperature rise is 2 to 7/spl deg/C hotter than for full-load sinusoidal currents. The greatest difference recorded between the average winding temperature and the hot-spot temperature was 7/spl deg/C, significantly less than the 15/spl deg/C allowance given in the standards. This study indicates that the present standard for sizing small distribution transformers supplying nonsinusoidal currents appears to provide good estimations of load capability.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.