Abstract

A comprehensive techno-economic evaluation is evaluated based on an innovative compound ejector-heat pump system with PV/T (photovoltaic thermal) waste heat-driven. The aim of the system is simultaneous data centre cooling and waste heat recovery for district heating to reduce residential greenhouse gas emissions. The new system avoids the ejector pump by combining PV/T waste heat with an evaporative-condenser as an ejector driving force, considering several low global warming potential alternatives to R134a. The simulation indicates that the proposed system presents a remarkable difference in all investigated refrigerants’ overall system coefficient of performance (COP). Particularly, R515B presents the highest increase in COP, 54% and 49% in cooling and heating modes, respectively. It also provides the highest electricity consumption reduction, 84.1 MWh yearly. Moreover, the system improves the data centre power usage effectiveness (PUE) index from 10 to 19%. In financial terms, the shortest payback period (6.3 years) is obtained with R515B, followed by R515A and R1234ze(E).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.