Abstract
The switching of HV motor circuits in the megawatt range can cause large overvoltages on motor terminals. The amplitude of the resulting voltage spikes depends on breaker type and circuit characteristics. If the amplitude of switching overvoltages exceeds the basic insulation level of the motor, overvoltage protection circuitry should be installed to prevent a motor insulation failure. The decision whether overvoltage protection circuitry (surge pack) must be installed requires a prediction of the overvoltage level. This paper deals with switching overvoltages in motor circuits with a unit transformer between switchgear and motor. Overvoltages of motor circuits were simulated using specially developed simulation models. The results of three case studies revealed a large impact of cabling and transformer on motor overvoltages. In most of the cases, a unit transformer connected between switchgear and motor will provide an overvoltage protection to the motor. However, the transformer can also be a main cause of large overvoltages when connected to cables of specific length and capacitance. The paper provides some simple rules to recognize such critical configurations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.