Abstract

The switching moving boundary (SMB) scheme is widely used for numerical simulation of heat exchangers, especially in vapour compression refrigeration system. The method divides the heat exchanger into up to three zones (superheated vapour, two-phase fluid and subcooled liquid), depending on the operating conditions and treats each as a lumped-parameter system. During transients the number of zones may vary, and suitable switching criteria and related threshold values must be given, for this change to occur. Also, variables for the zones momentarily phased out need to be tracked, to allow smooth operation of the model. In this work, a switching moving boundary model of a brazed plate condenser in counter-flow arrangement is studied to obtain some useful guidelines for the selection of the optimal switching thresholds. It is shown that these values influence both the accuracy and the numerical robustness of the model; moreover an appropriate selection of these parameters may allow the usage of a fixed-step solver, which is more suitable for real-time simulations.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.