Abstract
The presence of dust and coastal salt water found in a high moisture content environment can affect the stability of bushings in power transformers. This problem leads to transformer shut down and in severe conditions it can cause transformer expulsion. To eliminate this problem, a superhydrophobic modified-polyurethane coating was fabricated that contained easy cleaning property. Final coating had contact angles higher than 150° and CAH (Contact Angle Hysteresis) less than 10 degrees. The coating indicated good UV durability and mechanical robustness which was investigated by an abrasion test. It could pass acid rain and dry lightning impulse voltage tests. The best results were attained with the formulation containing 8 wt% nanosilica.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.