Abstract

A subsynchronous eleсtromechanical resonance in autonomous power systems is caused by the coincidence of the natural frequency of power network and one of the natural frequencies of turbogenerator unit in the electrical power plant. The occurrence and development of subsynchronous resonance causes subsynchronous oscillations of generators rotors, which are dangerous for shaft elements of turbogenerator units. Besides that, load angle oscillations having small amplitude under frequencies of 10-15 Hz create radial vibrations in bearing supports of turbogenerator units. The vibrations cause the emergency disconnection by vibration protection. In this paper the feature of subsynchronous resonance development in autonomous power system is present in the load power uncontrolled asynchronous motors and a large amount of similar frequency-controlled asynchronous various power drives through numerical simulations are discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call