Abstract
In recent years, the integration of renewable energy into power grid has gained prominence among researchers and scientists due to the growing energy demand and the depletion of fossil fuels. This paper would analyse the Huong Khe 35-kV medium voltage distribution network, in which 373E18.8 and 374E18.8 feeders are selected, to study the effects of the distributed Photovoltaics (PV) systems on the voltage quality and power losses on the grid such as overvoltage, reverse power, and increased power loss. The simulation results might solve the voltage quality and power loss problems. In addition, the results of different scenarios are examined. Using the Electrical Transient and Analysis Program (ETAP) software, we discussed how PV plants affected each scenario's voltage profile and power losses in the feeders. This study then provides solutions for those challenges using tap-changers of the substation from 37.5 kV to 36.5 kV and curtailment. Therefore, both the voltage quality and power loss problems have been solved.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.