Abstract

In general, the current leads of high voltage superconducting apparatuses cooled by liquid nitrogen are exposed to gaseous insulation media. Therefore, the investigation on the electrical breakdown characteristics of gaseous insulation media should be performed to develop electrically reliable high voltage superconducting power apparatuses. In this study, the lightning impulse breakdown tests on gaseous insulation media are conducted by using sphere-to-plane electrode systems made of stainless steel. Also, the lightning impulse breakdown voltage tests on gaseous insulation media according to various pressures are performed. The experimental results show that the electrical breakdown characteristics under lightning impulse voltage are affected by the gap length between electrode systems, the size of electrodes, and the field utilization factors. From these results, the electrical insulation design criteria to estimate the electrical breakdown voltage are established. The results are expected to be applicable to the design of current leads for high voltage superconducting apparatuses.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.