Abstract
Abstract In this paper, hot smoke test was carried out in the atrium of 60m high in Shanghai Tower, the law of fire smoke movement and smoke control effect has been studied under different fire release rate and different ventilation conditions. In this paper, the Influence of different air supply volume on mechanical smoke exhaust in the atrium of Shanghai Tower has also been studied by numerical simulation. The results showed that: in the tall atrium, smoke rise rapidly with the speed of 2-3 m/s because of “chimney effect”; Because of the “thermal barrier effect”, when the fire power is small, the smoke tends to subside and cannot be effectively discharged; When air supply volume is 50% of smoke exhaust, it is beneficial to exhaust smoke.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.