Abstract
Unbalanced input voltages would make doubly fed induction generator (DFIG)-based wind turbine operating performance deteriorate, such as shaft tremble, temperature increasing, and so on, even make it cut out of the power grid. Meanwhile, without proper control the power ripples generated from wind turbines may further aggravate power grid. Considering the unbalanced conditions, DFIG was modeled in dual synchronous reference frame (SRF), namely the positive one and the negative one, based on which the dual PI current controllers were designed. To implement the dual current control, the sensing variables were divided into positive and negative sequence components, which were controlled in positive and negative SRF respectively. At the same time, to synchronize with the positive and negative sequence voltage components, a phase latch loop (PLL) control was designed. Experimental results on 11kW DFIG wind turbine test bed validated the designed control system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.