Abstract
Point-supported glazing assemblies are widely used in modern buildings for aesthetic elegance, as well as for economic reasons. However, the formation of vents caused by glass breakage could aggravate ventilation controlled compartment fires. The point-covered area generally varies and may constitute potential fire hazards. Accordingly, it is necessary to investigate the fire performance and breakage mechanisms in various point-covered areas. In this study, a total of 12 tests, including three various point-covered area glazing, were heated by a 200 × 200 mm2 pool fire. The breakage time, glass surface and air temperatures, incident heat fiux, and crack initiation and final fall out ratio were obtained. The critical conditions for the three aforementioned various point-covered area glazing were determined. The reference breakage times, tr, which were calculated by assigning a failure probability of 0.1 to the two-parameter Weibull distribution were 119, 140, and 166 s. It was established that a relatively small point-covered area glazing can survive longer; the smaller the point-covered area was, the larger the final fallout ratio of glazing assemblies will be. Numerical simulations were performed to investigate the stress distribution on the glass pane, with breakage times well predicted. Accordingly, these results have implications on the fire resistance design for point-supported glazing assemblies.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.