Abstract

Large generators have high effective X/R ratios and combined with other generator time constants and parameters, a current zero may not be obtained at the time of contact parting, i.e., the dc component of the short-circuit current at the contact parting time is higher than the peak ac component. This is well documented in the current literature. The paper presents calculations of the generator source short-circuit currents of a 234 MVA generator using ANSI/IEEE and IEC standards and EMTP simulation. The results are compared and the application of a generator breaker to meet the requirements of calculated duties are discussed. It shows considerable differences in the results, depending upon the method of calculation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.